SciOp

EUROPEAN SOUTHERN OBSERVATORY

La Silla Observatory

SCIENCE OPERATION DEPARTMENT


SciOp


EMMI control device:
User's Requirements

LSO-URS-ESO-90400-1/1.0

Prepared O.Hainaut/A.Macchino
2002-09-12
Reviewed R.Parra 2002-09-13
Released Olivier Hainaut 2002-09-13

Revision History

0.1
2002-09-12 first draft,
1.0
2002-09-13 include review comments, released

1.- INTRODUCTION

1.1- PURPOSE and SCOPE

This document constitutes the user's requirement for the EMMI Control Box

1.2-  ACRONYMS AND DEFINITIONS

EMMI: ESO Multi-Mode Instrument on the NTT
RITZ: Remote Integrated Telescope Zentrum

2.- INTRODUCTION: Current status

Currently, a "hard" reset of EMMI, aka "Power Cycle" has to be perfomed locally by a trained operator. The current procedure is the following:


With the move of the control room to the RITZ, this procedure would imply an operator to leave the building, come up to NTT and perform the procedure, then back to thee RITZ to check the status.

Moreover, the procedure is tricky, in the sense that the order and delay between operations has to be strictly followed, otherwise the system(s) might not get properly initialized.

It is therefore desirable to make this procedure more automatic.

3- REQUIREMENTS

An additional control device -here after EMMI Control Device- should be implemented, that would


This device must have a "local/remote" mode switch.

In local mode, the [OFF] and [ON] commands are sent thru buttons on the chassis. The device contains the "intelligence" to execute the proper sequence.

In remote mode, the device is commanded through sofware orders. From the VLT SW control point of view, this device is attached to the lemcal LCU (which "belongs" to the EMMI instrument, and currently has very little load; moreover, lemcal is already in charge of anlther side task of EMMI, i.e. the shutter status report). The only signal needed is one sigle bit, with the following convention:
0 = ON
1 = OFF
Changing the status of that bit will cause the device to start and execute the corresponding sequence. Corresponding sofware commands will have to be requested from SWC.

Notes:
- any local intervention on ADAB VME will imply that the device is set to Local (SciOp and TElMa operation procedures will have to be updated).
- the actual 1/0 convention for the control bit needs to be discussed with SWC.


--oOo--